AS-Interface power supply VAN-115/230AC-K19

VAN-115/230AC-K19
  • Up to 2.8 A output load
  • Power factor correction
  • Electronic overload protection and display
  • LED operating display
  • AS-Interface data decoupling
  • PELV/SELV
  • NEC Class 2 Power Supply

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  VAN-115/230AC-K19

Productbeschrijving
AS-Interface power supply, data decoupling, 2,8 A
General specifications
UL File NumberE223176
MTBF221 a
Indicators/operating means
LED AS-i okLED green:
ON: AS-Interface voltage OK
OFF: overload or no supply voltage
Electrical specifications
Fusing2.5 AT (not replacable)
Capacity factor> 0.5
Rated operating voltagenominal: 100 ... 120 VAC/220 ... 240 VAC
permissible: 85 ... 132 VAC/184 ... 264 VAC
Rated operating current2.0 A at 115 VAC
0.9 A at 230 VAC
Supply frequency47 ... 63 Hz
Efficiency90.5 % (230 VAC, 2.8 A)
Output
Current limit> 3.2 A
Voltage30.55 VDC ± 3 % fixed setting
Current2.8 A
Residual ripple≤ 50 mVss (500 kHz bandwidth, 50-Ω-measurement with ohmic load)
Short-circuit currentmin. 3.2 A, max. 4.6 A
Compliance with standards and directives
Directive conformity
Low Voltage Directive 2006/95/ECEN 60950-1:2006, EN 61204-3:2001
EMC Directive 2004/108/ECEN 61000-6-2:2005, EN 61000-6-3:2007, EN 50295:1999
Standard conformity
Electromagnetic compatibilityEN 61000-6-2:2005; EN 61000-6-3:2007
AS-InterfaceEN 50295:1999, IEC 62026-2:2006
Mech. capacityEN 60068-2-6:2008
Shock and impact resistanceEN 60068-2-27:1995
Ambient conditions
Ambient temperature-10 ... 70 °C (14 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Shock and impact resistance15g/6 ms
10g/11 ms
Vibration resistance2 ... 17,8 Hz / 1.6 mm
17.8 ... 500 Hz / 2.0 g
Pollution degree2 (EN 60950)
Mechanical specifications
Degree of protectionIP20
Protection classI, Protective conductor connection necessary
ConnectionConnection terminals, max. conductor cross-section 0.5 ... 6 mm2 (20-10 AWG), Stripping length 7 mm
Massapprox. 500 g
Dimensions
Height124 mm
Width49 mm
Length102 mm
MountingDIN mounting rail

Classifications

SystemClasscode
ECLASS 13.027040301
ECLASS 12.027040301
ECLASS 11.027040301
ECLASS 10.0.127040301
ECLASS 9.027040301
ECLASS 8.027040301
ECLASS 5.127040301
ETIM 9.0EC002540
ETIM 8.0EC002540
ETIM 7.0EC002540
ETIM 6.0EC002540
ETIM 5.0EC002540
UNSPSC 12.139121004

Details: VAN-115/230AC-K19

Product Documentation: VAN-115/230AC-K19

Taalkeuze:
Brief InstructionsTaalBestandstypeBestandsgrootte
Instruction leaflet / BeipackzettelALLPDF262 KB

Design / Simulation: VAN-115/230AC-K19

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP16846 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ80 KB

Approvals: VAN-115/230AC-K19

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
US CA ULE223176ALLLINK---
US CA ULCoC E223176 RptRef E223176-20070416ALLPDF444 KB
Worldwide AS-International Association AS-Interface92901ALLPDF585 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4815AALLPDF164 KB

Aanverwante producten: VAN-115/230AC-K19

Accessories
AS-Interface Power supply and network checking utilityfa
Gratis Download: Whitepaper over TCP-gebaseerde communicatieprotocollen (pdf)

Dit gratis whitepaper vergelijkt de verschillende TCPgebaseerde -communicatieprotocollen (AMQP, OPC UA, MQTT, REST API) die zich overal hebben ingeburgerd en als sleuteltechnologieën voor IIoT en Industrie 4.0 worden beschouwd. Download uw gratis exemplaar!

As-interface productportfolio

Ontdek ons volledig As-interface productportfolio.