AS-Interface analog module VBA-4E-G11-I-F

VBA-4E-G11-I-F
  • Addressing jack
  • Function display for bus, internal and external sensor power supply, inputs
  • Supply for inputs from AS-Interface or auxiliary voltage
  • Degree of protection IP68 / IP69K
  • Accuracy ± 0.1 %
  • Integrated shielding
  • Channel-specific input monitoring

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  VBA-4E-G11-I-F

Productbeschrijving
G11 analog module, 4 analog current inputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
ProfileS-7.3.E
IO code7
ID code3
ID1 codeF
ID2 codeE
UL File NumberE223772
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: peripheral fault
LED ANALOGstatus of input signal; LED yellow
off: not active
on: signal within measuring range
flashing: signal outside of measuring range
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INT/EXTstatus display input supply; LED green
green: input supply from AS-Interface
off: input supply from auxiliary voltage
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 60 mA (without sensors) / max. 200 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 Inputs
0/4 ... 20 mA
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT)
Current loading capacity≤ 140 mA from AS-Interface; overload and short-circuit resistant
≤ 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected
Input resistancemax. 70 Ω
Accuracy0.1 % of full-scale value
Resolution16 Bit
Temperature influence0.0025 %/K of input signal range
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black
Inputs: M12 round connector
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
Dimensions
Height35 mm
Diameter85 mm
MountingMounting plate

Classifications

SystemClasscode
ECLASS 13.027242601
ECLASS 12.027242601
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 9.0EC001596
ETIM 8.0EC001596
ETIM 7.0EC001596
ETIM 6.0EC001596
ETIM 5.0EC001596
UNSPSC 12.139121535

Details: VBA-4E-G11-I-F

Informative Literature: VBA-4E-G11-I-F

Taalkeuze:
LiteratureTaalBestandstypeBestandsgrootte
Application Report - Automating Material Handling Systems for Airports with AS-InterfaceENGPDF272 KB

Product Documentation: VBA-4E-G11-I-F

Taalkeuze:
Brief InstructionsTaalBestandstypeBestandsgrootte
Instruction leaflet / BeipackzettelALLPDF885 KB
Manuals
Manual VBA-4E-G11-I-FENGPDF1676 KB

Design / Simulation: VBA-4E-G11-I-F

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP4756 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VBA-4E-G11-I-F

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
Canada, USA ULCoC 20141115-E223772ALLPDF342 KB
EU Ecolab Material ResistanceECOLABALLPDF1797 KB
Worldwide AS-International Association AS-Interface94203ALLPDF116 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2931BALLPDF119 KB

Aanverwante producten: VBA-4E-G11-I-F

Accessories

Blind plug for M12 socketsfa

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
Connecting cable, M12 to M12, PUR cable, 4-pin, bridged, shieldedfa
Gratis Download: Whitepaper over TCP-gebaseerde communicatieprotocollen (pdf)

Dit gratis whitepaper vergelijkt de verschillende TCPgebaseerde -communicatieprotocollen (AMQP, OPC UA, MQTT, REST API) die zich overal hebben ingeburgerd en als sleuteltechnologieën voor IIoT en Industrie 4.0 worden beschouwd. Download uw gratis exemplaar!

AS-i-schakelkastmodule KE5 – Gebruiksgemak en verbeterde bestuurbaarheid

Het unieke behuizingsconcept van de nieuwe KE5-schakelkastmodule biedt duidelijke zichtbaarheid en vereenvoudigt montage, aansluiting en onderhoud in schakelkasten en junction boxes.

As-interface productportfolio

Ontdek ons volledig As-interface productportfolio.