Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
De complete datasheet als PDF downloaden:
Productbeschrijving |
---|
G20 module 4 inputs/3 outputs |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
UL File Number | E223772 "For use in NFPA 79 Applications only" | |
MTBF | 110 a | |
Indicators/operating means | ||
LED FAULT | Fault indication; red LED Red: communication error or address is 0 Flashing red: overload at motor supply or overload at outputs, or external auxiliary voltage UAUX not present |
|
LED PWR | AS-Interface voltage; green LED Green: voltage OK Flashing green: address is 0 or overload at motor supply, or overload at outputs, or external auxiliary voltage UAUX not present |
|
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
LED IN | switching state (input); 4 LED yellow | |
LED OUT | Switching state (output); 3 LED yellow | |
Electrical specifications | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 35 mA | |
Input | ||
Number/Type | 4 Inputs (PNP), DC | |
Supply | from external auxiliary voltage UAUX | |
Input current | ≤ 8 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 0 (undamped) ≤ 0.5 mA 1 (damped) ≥ 2.0 mA |
|
Signal delay | < 1 ms (input/AS-Interface) | |
Output 1 | ||
Number/Type | 3 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from external auxiliary voltage UAUX | |
Current | 500 mA per output | |
Voltage | ≥ (UAUX - 0.5 V) | |
Output 2 | ||
Number/Type | Motor supply | |
Supply | from external auxiliary voltage UAUX | |
Current | TB < 40 °C: 2 A continuously, 5 A briefly (< 0.5 s) TB < 60 °C: 2 A continuously, 3 A briefly (< 0.5 s) |
|
Voltage | ≥ (UAUX - 0.5 V) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Input | EN 61131-2:2007 | |
Emitted interference | EN 61000-6-4:2007 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.A.E | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | E | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
|
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
|
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
|
Ambient conditions | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP54 according to EN 60529 | |
Connection | AS-Interface, AUX: Insulation piercing technology Yellow flat cable/black flat cable Inputs/outputs: 8-pin M8 round plug connector, bushing contacts, screw-locking Motor supply: 4-pin M12 round plug connector, bushing contacts, screw-locking, T-coded |
|
Mass | 260 g | |
Dimensions | ||
Height | 27.5 mm | |
Width | 152 mm | |
Length | 53.3 mm | |
Mounting | 2 clips with ∅ 8 mm drill hole | |
Cable length | 1 m | |
Note | The flat cable routing is designed for 100 actuation cycles |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Brief Instructions | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 557 KB |
CAE | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 364 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
AS-i-schakelkastmodule KE5 – Gebruiksgemak en verbeterde bestuurbaarheid
Het unieke behuizingsconcept van de nieuwe KE5-schakelkastmodule biedt duidelijke zichtbaarheid en vereenvoudigt montage, aansluiting en onderhoud in schakelkasten en junction boxes.