General specifications |
Signal type | Digital Output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
Supply |
Rated voltage | 15 ... 30 V DC , loop powered |
Power dissipation | 0.8 W |
Input |
Connection side | control side |
Connection | terminals 7, 8, 9 |
Input voltage | 15 ... 30 V DC |
Input current | ≤ 21 mA per channel |
Output |
Safety note | Attention! Combination of output Ex i with output not Ex i is not permitted. If load voltage > 50 V, de-energize before removing the terminals. |
Connection side | field side |
Connection | terminals 1, 2, 3; 4, 5, 6 |
Contact loading | 230 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Energized/De-energized delay | approx. 10 ms / approx. 5 ms |
Mechanical life | 5 x 106 switching cycles |
Transfer characteristics |
Switching frequency | < 10 Hz |
Galvanic isolation |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LEDs |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | DMT 00 ATEX E 016 |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Output | Ex ia |
| Voltage | 60 V |
| Current | 2 A |
Input | |
| Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) |
Output | |
| Contact loading | 50 V AC/2 A ; 40 V DC/2 A (TÜV 00 ATEX 1621 X) |
Certificate | TÜV 00 ATEX 1621 X |
| Marking | II 3G Ex nA nC IIC T4 |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Output/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 60 V |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
FM approval | |
| Control drawing | 116-0261 |
CSA approval | |
| Control drawing | 116-0156 |
IECEx approval | |
| IECEx certificate | IECEx BVS 10.0025 |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |