Serviceline Industrial Sensors
Serviceline Explosion Protection
暂不可售
暂不可售

Valve Coupler FD0-VC-EX4.FF

FD0-VC-EX4.FF
  • For four intrinsically safe valves with position sensors
  • Installation in Zone 1 and Zone 2
  • Valves in Zone 0
  • Connection to fieldbus acc. to FISCO or Entity
  • For FOUNDATION Fieldbus H1
  • PCS integration via device description and function blocks
  • Monitors lead breakage and short circuits
  • Valve monitoring and diagnostics integrated
  • Conducts partial stroke testing

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

下载PDF版完整参数表:


技术参数节选  FD0-VC-EX4.FF

General specifications
Design / MountingOutside installation
Fieldbus connection
FOUNDATION Fieldbus
ConnectionConnection +, -
Rated voltage9 ... 32 V
Rated currentmax. 23 mA
Baud rate31.25 kBit/s
ProtocolIEC 61158-2
Terminal "S"only for the connection of the cable screen (BUS) and/or the potential compensation
Terminal "PA"only for the connection of the cable screen (sensor interface) and/or grounding
Grounding plateonly for the connection of the potential compensation
Field circuit
Inputs
Connection8, for binary sensors: terminals 3, 4, 7, 8, 11, 12, 15, 16
Sensor supply voltage5 V
Sensor supply current5 mA
Time delay before availability2 ms
Max. cycle timemax. 160 ms
Outputs
Connectionterminals 1+, 2-; 5+, 6-; 9+, 10-; 13+, 14-
Output voltage6.4 ... 7.9 V
Output rated operating current1.5 mA
Holding current1 mA
Galvanic isolation
Foundation Fieldbus/Field circuitsafe galvanic isolation acc. to EN 50020, voltage peak value 60 V
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Galvanic isolationEN 60079-11
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC/EN 60529
Fieldbus standardEN 50170/2
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Core cross-sectionBus cable: ∅ 5 mm ... 10 mm
cable sensors/valve: ∅ 4 mm ... 8 mm
Housing187 mm x 129 mm x 46 mm
Degree of protectionIP65
Installation positionCable glands downwards
Massapprox. 290 g
Mountingwall mounting
Data for application in connection with hazardous areas
EU-Type Examination CertificatePTB 98 ATEX 2210
MarkingEx-Hexagon II 2G (1) Ex ia [ia Ga] IIC T4 Gb ,
Ex-Hexagon II (1D) [Ex ia Da] IIIC ,
Ex-Hexagon II 3G Ex ic IIC T4 Gc ,
Ex-Hexagon II (3D) [Ex ic Dc] IIIC
Field-side
Voltage Uo9 V
Current Io44 mA
Power Po99 mW
FOUNDATION Fieldbus
Voltage Ui24 V
Current Ii380 mA
Power Pi5.32 W
Rated voltage9 ... 32 V
Rated current23 mA
FDE (Fault Disconnect Equipment)6.7 mA
Terminal "S"only for the connection of the cable screen (BUS) and/or the potential compensation
Terminal "PA"only for the connection of the cable screen (sensor interface) and/or grounding
Grounding plateonly for the connection of the potential compensation
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012
International approvals
IECEx approvalIECEx TUN 04.0002
Approved forEx ia [ia Ga] IIC T4 Gb ,
[Ex ia Da] IIIC ,
Ex ic IIC T4 Gc ,
[Ex ic Dc] IIIC

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008
Product category / 产品类的阀位耦合器

Details: FD0-VC-EX4.FF

Informative Literature: FD0-VC-EX4.FF

选择语言:
Literature语言文件类型文件大小
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: FD0-VC-EX4.FF

选择语言:
System Descriptions语言文件类型文件大小
Planning and integration: Compatibility list of sensors and pilot valvesENGPDF50 KB
Manuals
Manual FD0-VC-Ex4.FFENGPDF1054 KB

Approvals: FD0-VC-EX4.FF

选择语言:
Certificates证书号码语言文件类型文件大小
Europe PTB II 2 G (1) II (1D) II (3D) II 3 G ATEXPTB 98 ATEX 2210ALLPDF1378 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0002ALLLINK---
Worldwide Fieldbus FoundationIT035200ALLPDF257 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitätserklärung (P+F)DOC-0812BALLPDF88 KB

Software: FD0-VC-EX4.FF

选择语言:
Device Description Files/DriversRelease Info文件类型文件大小
DD/CFF files, Device Revision 1 / DD/CFF-Dateien, Device Revision 10102/010201ZIP47 KB
DD/CFF files, Device Revision 2, DD Revision 2 / DD/CFF-Dateien, Device Revision 2, DD Revision 20202/020103ZIP57 KB

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …