Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Téléchargez ici la fiche technique complète en PDF:
Description produit |
---|
Segment protector, junction box for fieldbus with short-circuit protection, Field junction box, module for DIN rail mounting |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Installation in hazardous area | Zone 1 / Div. 2 | |
Fieldbus connection | ||
Power dissipation | 250 mW | |
Main cable (Trunk) | ||
Cable entry type | screw terminal , fixed | |
Rated voltage | 9 ... 32 V DC | |
Outputs | ||
Number of outputs | 12 | |
Cable entry type | screw terminal , fixed | |
Rated voltage | max. 32 V | |
Rated current | max. 40 mA | |
Short-circuit current | max. 52 mA | |
Self current consumption | max. 9 mA | |
Voltage drop main cable/outputs | max. 1.3 V | |
Terminating resistor | selectable 100 Ω integrated | |
Surge protection | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V | |
Indicators/operating means | ||
LED PWR | green: Fieldbus voltage > 10 V | |
LED CHANNEL ERROR | red flashing: short-circuit | |
LED COM | yellow: bus activity | |
LED TERM ON | yellow: termination activated | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 5 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Connection type | screw terminal , fixed | |
Core cross section | max. 2.5 mm2 / AWG 12-24 | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | 800 g | |
Dimensions | ||
Height | 100 mm | |
Width | 216 mm | |
Depth | 50 mm | |
Mounting | DIN rail mounting | |
Coating | resin filled | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 04 ATEX 2100 X | |
Marking | II 2 G Ex eb mb IIC T4 Gb | |
Maximum values | ||
Rated voltage | ≤ 35 V | |
Prospective short-circuit current | 100 A | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-7:2015+A1:2018 , EN 60079-18:2015+A1:2017 | |
International approvals | ||
IECEx approval | IECEx PTB 05.0010X | |
Approved for | Ex eb mb IIC T4 Gb | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242610 |
ECLASS 12.0 | 27242610 |
ECLASS 11.0 | 27242610 |
ECLASS 10.0.1 | 27242610 |
ECLASS 9.0 | 27242610 |
ECLASS 8.0 | 27242610 |
ECLASS 5.1 | 27242601 |
ETIM 9.0 | EC001601 |
ETIM 8.0 | EC001601 |
ETIM 7.0 | EC001601 |
ETIM 6.0 | EC001601 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Literature | Langue | Type de fichier | Taille |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Langue | Type de fichier | Taille |
---|---|---|---|
Manuel d'instructions | FRA | 222 KB |
Certificates | Identification | Langue | Type de fichier | Taille |
---|---|---|---|---|
Brasil TUV Rheinland Brazil Ex e | TÜV 13.1153 X | ALL | 1179 KB | |
China SITIIAS CCC Ex Certificate | 2021322310003756 (Singapore) | ALL | 831 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe PTB ATEX Category 2 G | PTB 04 ATEX 2100X | ALL | 374 KB | |
PTB IECEx Certificate of Conformity | IECEx PTB 05.0010X | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-0207EFRA | FRA | 1134 KB |