Servizio assistenza Sensori Industriali
Telefono: +39 039 69599 1
Fax.: +39 039 69599 30
Servizio assistenza Protezione contro le esplosioni
Telefono ++39 039 62921
Fax ++39 039 6292 390

Protection Module for Surge Protection Barrier M-LB-4282.M

M-LB-4282.M
  • Protection module for 2 signal lines
  • Nominal voltage 230 V
  • Protection module for non-grounded signal lines
  • Max. surge current (8/20 µs) 6 kA
  • Uninterruptable operation (auto reset)
  • Status indication
  • Mounting on base module, pluggable
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  M-LB-4282.M

General specifications
Number of protected signal lines2
Topologynon-grounded
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Electrical specifications
Connectionvia base module
Leakage current< 50 nA bei Uc , line-line
< 50 nA bei Uc , line-earth
Nominal voltage230 V
Maximum continuous operating voltage250 V AC and 320 V DC
Nominal load current3 A at 80 °C (176 °F)
Series resistance0 Ω per line
Impulse discharge current (10/350 µs)0.5 kA per line
Nominal discharge current (8/20 µs)3 kA per line
Total discharge current (8/20 µs)6 kA
Voltage protection level
max. 1100 V line-earth for nominal discharge current In
Impulse reset time< 30 ms
Cut-off frequency200 MHz , line-line
Indicators/settings
Display elementsstatus display
operating state (green)
fault indication (red)
Conformity
Degree of protectionIEC 60529:2013
Functional safetyIEC/EN 61508:2010
Surge protective devices for low voltageEN 61643-21:2001+A1:2009+A2:2013
IEC 61643-21:2001+A1:2008+A2:2012
Ambient conditions
Ambient temperature-40 ... 80 °C (-40 ... 176 °F)
Storage temperature-40 ... 80 °C (-40 ... 176 °F)
Relative humiditymax. 95 % , without condensation
Corrosion resistanceacc. to ISA-S71.04, severity level G3
Mechanical specifications
Degree of protectionIP20
Connectionvia base module
Material
HousingPolyamide PA 6.6
Massapprox. 14 g
Dimensions6 x 45 x 54 mm (0.24 x 1.77 x 2.15 inch) (W x H x D)
Height45 mm
Width6 mm
Depth54 mm
Mountingpluggable in base module for mounting on 35 mm DIN mounting rail
Data for application in connection with hazardous areas
EU-type examination certificate
Internal capacitance
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027171202
ECLASS 12.027171202
ECLASS 11.027130805
ECLASS 10.0.127130805
ECLASS 9.027130805
ECLASS 8.027130805
ECLASS 5.127130801
ETIM 9.0EC000941
ETIM 8.0EC000941
ETIM 7.0EC000941
ETIM 6.0EC000941
ETIM 5.0EC000941
UNSPSC 12.139121610

Details: M-LB-4282.M

Product Documentation: M-LB-4282.M

Language Selection:
Brief InstructionsLinguaFile tipoDimensioni
Instruction leaflet / BeipackzettelALLPDF5479 KB
Safety and Security Documentation
Functional Safety ManualENGPDF1990 KB

Design / Simulation: M-LB-4282.M

Language Selection:
CADLinguaFile tipoDimensioni
CAD 3-D / CAD 3-DALLSTP1283 KB
CAE
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ698 KB

Approvals: M-LB-4282.M

Language Selection:
Declaration of ConformityCertificato NumeroLinguaFile tipoDimensioni
EU Declaration of Conformity (P+F)TDOC-7141_ITAITAPDF175 KB

Prodotti associati : M-LB-4282.M

Accessory of
Surge protection for 2 signal lines, Nominal voltage 230 V, Surge protection barrier for non-grounded signal lines, Max. surge current (8/20 µs) 6 kA, Uninterruptable operation (auto reset), Status indication, Modular design, pluggable, Up to SIL 3 acc. to IEC/EN 61508, Modularity: two-piece, Number of protected signal lines: 2, Topology: non-grounded, Safety Integrity Level (SIL): SIL 3, Nominal discharge current (8/20 µs): 3 kA per linepa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.

Hub sicurezza funzionale di Pepperl+Fuchs

Diverse centinaia di prodotti con valutazione SIL/PL, strumenti gratuiti e brochure in un unico posto: l'hub "Sicurezza funzionale" è il tuo punto di partenza per l'implementazione delle funzioni di sicurezza.