Serviceline Industrial Sensors
联系客服
Serviceline Explosion Protection
联系客户服务

Alarm sounder PF-IS-SM-105

PF-IS-SM-105
  • ATEX, IECEx and UKEX approval
  • For use in Zone 0, 1, 2, 20, 21, 22 and mining applications
  • Max. output of 105 dB
  • Available with 32 tones and 2 stages
  • Recommended for fire, security and process control applications
  • Degree of protection: IP 66
  • Compliant with EN 54-3
  • Diode polarized and end of line resistor compatible

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

下载PDF版完整参数表:


技术参数节选  PF-IS-SM-105

产品阐述
Alarm Sounder 105 dB Ex ia IIC
Electrical specifications
Operating voltage16 ... 28 V DC , via zener barrier or galvanic isolator
Operating current21 mA @ 24 V DC max. - value measured with Zener barrier connected
Terminal capacity0.5 ... 2.5 mm2
FunctionAlarm sounder
Flash mode
Sound pressure level, maximum105 dB @ 1 m +/- 3 dB - sound 18 , 95 dB @ 3 m
Sound pressure level, nominal87 dB @ 1 m +/- 3 dB - sound 1
Number of sounds32
Number of stages2
Mechanical specifications
Enclosure coverfully detachable
Cover fixingStainless steel screws
Degree of protectionIP66
Cable entry face C
M20 quantity1
M20 typethru-holes
M20 infowithout entry devices (ordered separately)
Cable entry face E
M20 quantity1
M20 typeknockout
Material
EnclosurePolycarbonate UL94 V2
FinishRAL 3000 (red)
Sealnitrile O-ring
Seal insertNeoprene
Mass0.29 kg
GroundingInternal connection
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Data for application in connection with hazardous areas
EU-type examination certificateERO 24 ATEX 0014X
MarkingEx-Hexagon II 1 GD
Ex ia IIC T6 Ga
Ex ia IIIC T200 85°C Da
Ex-Hexagon I M1
Ex ia I Ma
Equipment
Voltage28 V max.
Current93 mA max.
Power660 mW max.
Internal capacitance0 µF max.
Internal inductance0 mH max.
International approvals
IECEx approvalIECEx EMT 24.0011X
UKCA approvalEMA 24 UKEX 0006X
Further approvalsavailable on request
Conformity
Degree of protectionEN 60529
CE marking2829
UKCA marking2503
General information
Scope of deliverydevice
Instruction leaflet
Gasket set
Allen wrench
anti-rotation grub screw
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessoriesCG.PIDS1.M20.PA.C.10.K01.LN55
SP.PE.M20.*

Classifications

SystemClasscode
ECLASS 13.027110509
ECLASS 12.027110509
ECLASS 11.027110509
ECLASS 10.0.127110509
ECLASS 9.027110509
ECLASS 8.027110509
ECLASS 5.127371220
ETIM 9.0EC002493
ETIM 8.0EC002493
ETIM 7.0EC002493
ETIM 6.0EC002493
ETIM 5.0EC001952
UNSPSC 12.139121314
Product category / 产品类的

Details: PF-IS-SM-105

Product Documentation: PF-IS-SM-105

选择语言:
Brief Instructions语言文件类型文件大小
Brief InstructionsENGPDF302 KB
Safety and Security Documentation
说明手册CHSPDF359 KB

Approvals: PF-IS-SM-105

选择语言:
Certificates证书号码语言文件类型文件大小
Europe Element Materials Technology ATEXERO24ATEX0014XALLPDF790 KB
United Kingdom Element Materials Technology UKEX Category II 1 GEMA24UKEX0006XALLPDF808 KB
Worldwide Element Materials Technology IECEx Certificate of ConformityIECEx EMT 24.0011XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (Pepperl+Fuchs)DOC-7882AALLPDF128 KB
UK Declaration of Conformity (Pepperl+Fuchs)DOC-7889AALLPDF126 KB

配套产品: PF-IS-SM-105

Accessories
1-channel, DC version, positive polarity, Working voltage 26.5 V at 10 µA, Series resistance max. 327 Ω, Fuse rating 50 mA, DIN rail mountable, Type: DC version, positive polaritypa
1-channel, DC version, positive polarity, Working voltage 26.5 V at 10 µA, Series resistance max. 341 Ω, Fuse rating 50 mA, DIN rail mountable, Replaceable back-up fuse, Type: DC version, positive polaritypa
2-channel, DC version, positive polarity, Working voltage 26.5 V at 10 µA, Series resistance max. 327 Ω, Fuse rating 50 mA, DIN rail mountable, With diode return, Type: DC version, positive polaritypa
2-channel, DC version, positive polarity, Working voltage 26.5 V at 10 µA, Series resistance max. 341 Ω, Fuse rating 50 mA, DIN rail mountable, Replaceable back-up fuse, With diode return, Type: DC version, positive polaritypa
2-channel, DC version, positive polarity, Working voltage 26.5 V at 10 µA, Series resistance max. 640 Ω, Fuse rating 50 mA, DIN rail mountable, With diode return, Type: DC version, positive polaritypa
1-channel isolated barrier, 24 V DC supply (loop powered), Current limit 45 mA at 10 V DC, Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: loop powered, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 1 x Valve, Field device [2]: 1 x audible alarm, Field device [3]: 1 x visual alarmpa
1-channel isolated barrier, 24 V DC supply (bus or loop powered), Output 45 mA at 10 V DC, Line fault transparency (LFT), Test pulse immunity, Housing width 12.5 mm, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 12.5 mm, Number of channels: 1-channel, Line fault transparency, Safety Integrity Level (SIL): SIL 3, Systematic capability (SC): SC 3, Rated voltage: 19 ... 30 V DC
loop powered, Type: logic input, Type [2]: field device supply, Test pulse immunity, Field device: 1 x Valvepa
2-channel isolated barrier, 24 V DC supply (loop powered), Current limit 45 mA at 10 V DC, Up to SIL 3 acc. to IEC/EN 61508, Housing width: 20 mm, Number of channels: 2-channel, Safety Integrity Level (SIL): SIL 3, Rated voltage: 20 ... 35 V DC , loop powered, Type: field device supply, Field device: 2 x Valve, Field device [2]: 2 x audible alarm, Field device [3]: 2 x visual alarm, Current: ≤ 45 mA, Voltage: ≥ 10 Vpa
For cables without armor, Thread M20, Thread length 10 mm, Ex eb and Ex tb certified, Blue marking for use with Ex i circuits, High impact-resistant polyamide material, Seal chloroprene, Suitable for operation in Zone 1, Zone 2, Zone 21 and Zone 22, Very large clamping range due to double sealing insert, Full impact resistance of 7 J according to IEC/EN 60079-0 for the full range without limitations, Cable type: non-armored cables, Thread size (TD): M20, Cable gland: high impact-resistant polyamidepa
Stopping plug for unused cable entries, High impact-resistant polyamide material, Thread M20, Hexagon head, Ex eb and Ex tb certified, Suitable for operation in Zone 1, Zone 2, Zone 21 and Zone 22, Full impact resistance of 7 J according to IEC/EN 60079-0 for the full range without limitations, Packaging unit: 50 pieces, without accessories, Thread size (TD): M20, Stopping plug: high impact-resistant polyamide, Marking: [exsign] II 2 GD
Ex eb IIC Gb
Ex tb IIIC Dbpa

We value your privacy!

We and our partners are using technologies like cookies and process personal data like the IP-address or browser information in order to personalize the advertising that you see. This helps us to show you more relevant ads and improves your internet experience. We also use it in order to measure results or align our website content. Because we value your privacy, we are herewith asking for your permission to use these technologies. You can always change/withdraw your consent later by clicking on the settings button on the left lower corner of the page.

Deny all cookies

We value your privacy!

Please select the group of cookies and scripts, that you consent to.

Functional
These cookies are necessary so that you can navigate through the pages and use essential functions (e.g. login).
Analytics
We use these cookies and scripts to measure the visits and clicks on our website in order to constantly improve it.
Marketing
These cookies and similar technologies are used to provide you with personalized and therefore relevant advertising content.