Servizio assistenza Sensori Industriali
Telefono: +39 039 69599 1
Fax.: +39 039 69599 30
Servizio assistenza Protezione contro le esplosioni
Telefono ++39 039 62921
Fax ++39 039 6292 390

Com Unit for FOUNDATION Fieldbus Modular I/O FB8210*

FB8210*
  • Interface between the I/O modules and the PCS/PLC
  • Com unit for 20 analog or 40 digital channels
  • Communication via FOUNDATION Fieldbus H1
  • HART communication via service bus
  • Configured via the process control system
  • Non-volatile memory for configuration and parameter settings
  • Quick communication set-up
  • Permanently self-monitoring
  • Outputs drive to safe state in case of failures
  • Supports multichannel I/O modules
  • Installation in suitable enclosures in Zone 1 or Zone 21
  • Module can be exchanged under voltage (hot swap)
  • Installation in suitable enclosures in Zone 1

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  FB8210*

Supply
Connectionbackplane bus
Rated voltage5 V DC , only in connection with the power supplies FB92**
Power consumption2 W
Auxiliary energy24 V DC
Trunk load 20 mA
Fieldbus connection
Fieldbus typeFOUNDATION Fieldbus H1
FOUNDATION Fieldbus
Connectionwired to Ex e terminals via backplane
Baud rate31.25 kBit/s , MBP
ProtocolH1 to IEC 1158-2
Station connectiondirectly at the trunk or via spur protector
Number of stations per bus line1 or 2, depending on the required response times
Number of channels per stationmax. 20 analog, max. 40 digital
Supported I/O modules5 slots, to be filled with (combinations possible):
1*08 digital input, 8-channel, NAMUR
3*05 analog input, 4-channel, 20 mA (HART via service bus)
4*05 analog output, 4-channel, 20 mA (HART via service bus)
5204 Pt100 RTD input, 4-channel
5205 thermocouple input, 4-channel
6305 relay output, 4-channel, 230 V
6306 relay output, 8-channel, 24 V
6*08 digital output, 8-channel, Ex i
6210-6215 digital output, 4-channel, Ex i power
* = variable (2=IS, 3=Ex e)
Bus lengthmax. 1900 m
(must not be exceeded by the sum of all trunk and spur lines)
Spur lengthmax. 120 m
(depending on the number of field devices. Modular I/O station = 1 field device)
Addressingvia PCS (software)
Internal bus
Connectionbackplane bus
Indicators/settings
LED indicatorLED green (power supply): On = operating, fast flash = cold start
LED red (collective alarm): On = internal fault, flashing = no fieldbus
LED yellow (operating mode): Flashing = active
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionvia backplane
Massapprox. 750 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-Type Examination CertificatePTB 97 ATEX 1074 U
MarkingEx-Hexagon II 2 G Ex d IIC Gb
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
EN 61241-11:2006
International approvals
ATEX approvalPTB 97 ATEX 1075

EAC approvalRussia: RU C-IT.MIII06.B.00129
Marine approval
Lloyd Register15/20021
DNV GL MarineTAA0000034
American Bureau of ShippingT1450280/UN
Bureau Veritas Marine22449/B0 BV

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: FB8210*

Informative Literature: FB8210*

Language Selection:
LiteratureLinguaFile tipoDimensioni
Application Report - Communication Redundancy for Uninterrupted OperationENGPDF529 KB
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field DevicesENGPDF208 KB
Application Report - Space Saving Extension for Existing PlantsENGPDF300 KB
Application Report - Using Remote I/O Systems for the Efficient Digitalization of PlantsENGPDF371 KB

Product Documentation: FB8210*

Language Selection:
System DescriptionsLinguaFile tipoDimensioni
Supported I/O modulesENGPDF31 KB
Safety and Security Documentation
Manuale di istruzioniITAPDF66 KB
Manuals
Manual - FB-Remote-I/O-SystemENGPDF5670 KB
Manual FF ComUnit 8x10ENGPDF1471 KB
Software Information
Software Product Note Remote I/O DTM / Softwareproduktschein Remote I/O DTMALLPDF256 KB

Design / Simulation: FB8210*

Language Selection:
CAELinguaFile tipoDimensioni
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ103 KB

Approvals: FB8210*

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
Bureau Veritas (Maritime) Marine22449/C0 BVALLPDF590 KB
DNV MarineTAA0000034ALLPDF110 KB
Europe PTB ATEX Category 2 GPTB 97 ATEX 1074UALLPDF2619 KB
Lloyd's Register MarineLR2003616TA-02ALLPDF557 KB
Worldwide Fieldbus FoundationIT048400ALLPDF149 KB

Software: FB8210*

Language Selection:
Device Description Files/Driversinformazioni sulla liberatoriaFile tipoDimensioni
DD & CFF Datei für LB/FB FF Remote IO / DD & CFF Datei für LB/FB FF Remote IO39/2007ZIP65 KB

Prodotti associati : FB8210*

Accessories
Device DTM, For Remote I/O systems, Frame application, like e. g. PACTware, must be installed separatelypa