Servizio assistenza Sensori Industriali
Telefono: +39 039 69599 1
Fax.: +39 039 69599 30
Servizio assistenza Protezione contro le esplosioni
Telefono ++39 039 62921
Fax ++39 039 6292 390
Non acquistabile
Non acquistabile

Modular Segment Protector for Cabinet Installation RM-SP*

RM-SP*
  • 2 outputs Ex nL, expandable to up to 26 with short-circuit protection
  • High-power trunk for high device count and long cable lengths
  • Segment Protector in Zone 2/Div. 2
  • Instruments in Zone 2/Div. 2
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Power, Com, and Error LEDs
  • Integrated overvoltage protection

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  RM-SP*

General specifications
Design / MountingCabinet installation
Fieldbus connection
Power dissipationsee table "Technical data depending on model"
Main cable (Trunk)
Rated voltage9 ... 31 V DC
Rated currentmax. 4.5 A
Outputs
Number of outputssee table "Technical data depending on model"
Rated voltagemax. 31 V
Rated currentmax. 43 mA
Short-circuit currentmax. 58 mA
Self current consumptionsee table "Technical data depending on model"
Voltage drop main cable/outputsmax. 1.3 V
Terminating resistor100 Ω external
Surge protectionTrunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
LED ERRred: short-circuit
LED PWRgreen: Fieldbus voltage > 10 V
LED COMyellow: bus activity
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typescrew terminals, removable
Core cross sectionmax. 2.5 mm2 /AWG 12-24
Housing materialPolyamide PA 66
Degree of protectionIP20
Mass75 g per device
Dimensions
Height94 mm
Width17.5 mm per device
Depth54 mm
MountingDIN rail mounting
Data for application in connection with hazardous areas
Main cable (Trunk)
Rated currentsee Statement of Conformity
Outputs
Voltage24 V for IIC gas group, defined by trunk voltage
32 V for IIB gas group
Current65 mA for IIC and IIB gas groups
Inductance0.25 mH for IIC and IIB gas groups
Capacitance60 nF for IIC and IIB gas groups
CertificateTÜV 11 ATEX 081152 X
MarkingEx-Hexagon II 3G Ex nA [nL] IIC T4
Directive conformity
Directive 94/9/ECEN 60079-15:2005 , EN 60079-0:2006
International approvals
UL approvalE106378
Approved forClass I, Division 2, Groups A, B, C, D
Certificates and approvals
Marine approvalDNV A-10798
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242601
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: RM-SP*

Informative Literature: RM-SP*

Language Selection:
LiteratureLinguaFile tipoDimensioni
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB
Guideline for Using Fieldbus Equipment in Zone 2ENGPDF830 KB

Product Documentation: RM-SP*

Language Selection:
Safety and Security DocumentationLinguaFile tipoDimensioni
Manuale di istruzioniITAPDF65 KB
Manuals
Manual Modular Segment ProtectorENGPDF775 KB

Approvals: RM-SP*

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
USA ULE106378 UL (QUZW)ALLLINK---
Worldwide Fieldbus FoundationDC064300ALLPDF29 KB

Ethernet-APL permette la comunicazione continua su tutti i livelli gerarchici. Maggiori informazioni sull'innovativa tecnologia …

Servizio informazioni RSS per aggiornamenti PANOS

Rimanete informati in merito al lancio di nuovi aggiornamenti software di PANOS, il sistema operativo per gli interruttori Ethernet-APL: Con il nostro Feed RSS riceverete una notifica e-mail nella casella di posta subito dopo il rilascio di un aggiornamento.

Dal processo decisionale alla pianificazione, l'installazione, la messa in servizio e la manutenzione: Scopri come ottenere il massimo dalla tua infrastruttura per bus di campo…