Valve Coupler FD0-VC-EX4.PA

FD0-VC-EX4.PA
  • For four intrinsically safe valves with position sensors
  • Installation in Zone 1 and Zone 2
  • Valves in Zone 0
  • Connection to fieldbus acc. to FISCO or Entity
  • For PROFIBUS PA
  • PCS integration with FDT/DTM technology
  • Monitors lead breakage and short circuits
  • Valve monitoring and diagnostics integrated
  • Conducts partial stroke testing
  • Conforms to PROFIBUS PA profile

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  FD0-VC-EX4.PA

General specifications
Design / MountingOutside installation
Fieldbus connection
PROFIBUS PA
ConnectionConnection +, -
Rated voltage9 ... 32 V
Rated currentmax. 23 mA
Baud rate31.25 kBit/s
ProtocolIEC 61158-2
Terminal "S"only for the connection of the cable screen (BUS) and/or the potential compensation
Terminal "PA"only for the connection of the cable screen (sensor interface) and/or grounding
Grounding plateonly for the connection of the potential compensation
Field circuit
Inputs
Connection8, for binary sensors: terminals 3, 4, 7, 8, 11, 12, 15, 16
Sensor supply voltage5 V
Sensor supply current5 mA
Time delay before availability2 ms
Max. cycle timemax. 160 ms
Outputs
Connectionterminals 1+, 2-; 5+, 6-; 9+, 10-; 13+, 14-
Output voltage6.4 ... 7.9 V
Output rated operating current1.5 mA
Holding current1 mA
Galvanic isolation
PROFIBUS PA/Field circuitsafe galvanic isolation acc. to EN 60079-11, voltage peak value 60 V
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Galvanic isolationEN 60079-11
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC/EN 60529
Fieldbus standardIEC 61158-2
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Core cross sectionBus cable: ∅ 5 mm ... 10 mm
Cable sensors/valve: ∅ 4 mm ... 8 mm
Housing187 mm x 129 mm x 46 mm
Degree of protectionIP65
Installation positionCable glands downwards
Massapprox. 290 g
Mountingwall mounting
Data for application in connection with hazardous areas
EU-type examination certificatePTB 98 ATEX 2210
MarkingEx-Hexagon II 2G (1) Ex ia [ia Ga] IIC T4 Gb ,
Ex-Hexagon II (1D) [Ex ia Da] IIIC ,
Ex-Hexagon II 3G Ex ic IIC T4 Gc ,
Ex-Hexagon II (3D) [Ex ic Dc] IIIC
PROFIBUS PA
Voltage24 V
Current380 mA
Power5.32 W
Rated voltage9 ... 32 V
Rated current23 mA
FDE (Fault Disconnect Equipment)6.7 mA
Terminal "S"only for the connection of the cable screen (BUS) and/or the potential compensation
Terminal "PA"only for the connection of the cable screen (sensor interface) and/or grounding
Grounding plateonly for the connection of the potential compensation
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012
International approvals
IECEx approvalIECEx TUN 04.0002
Approved forEx ia [ia Ga] IIC T4 Gb ,
[Ex ia Da] IIIC ,
Ex ic IIC T4 Gc ,
[Ex ic Dc] IIIC
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: FD0-VC-EX4.PA

Informative Literature: FD0-VC-EX4.PA

Language Selection:
LiteratureLinguaFile tipoDimensioni
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: FD0-VC-EX4.PA

Language Selection:
System DescriptionsLinguaFile tipoDimensioni
Planning and integration: Compatibility list of sensors and pilot valvesENGPDF50 KB
Manuals
Manual FD0-VC-Ex4.PAENGPDF956 KB
Software Information
Release Information FD0-VC-Ex4.PA DTMENGPDF406 KB
Release information DD/GSD filesENGPDF325 KB

Approvals: FD0-VC-EX4.PA

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
Europe PTB II 2 G (1) II (1D) II (3D) II 3 G ATEXPTB 98 ATEX 2210ALLPDF1378 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0002ALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitätserklärung (P+F)DOC-0812BALLPDF88 KB

Software: FD0-VC-EX4.PA

Language Selection:
Device Description Files/Driversinformazioni sulla liberatoriaFile tipoDimensioni
Device Driver / Gerätetreiber1.3ZIP259 KB
GSD / GSDRev. 1.5ZIP4 KB
Software Tools
FD0-VC-Ex4.PA DTM / FD0-VC-Ex4.PA DTM1.5.97.14ZIP20003 KB

Ethernet-APL permette la comunicazione continua su tutti i livelli gerarchici. Maggiori informazioni sull'innovativa tecnologia …

Servizio informazioni RSS per aggiornamenti PANOS

Rimanete informati in merito al lancio di nuovi aggiornamenti software di PANOS, il sistema operativo per gli interruttori Ethernet-APL: Con il nostro Feed RSS riceverete una notifica e-mail nella casella di posta subito dopo il rilascio di un aggiornamento.

Dal processo decisionale alla pianificazione, l'installazione, la messa in servizio e la manutenzione: Scopri come ottenere il massimo dalla tua infrastruttura per bus di campo…