Línea de servicio de Sensores Industriales
Teléfono: +34 94 453 50 20
Fax: +34 94 453 51 80
Atención al cliente para protección contra explosiones
Teléfono: +34 94 453 50 20
Fax: +34 94 453 51 80

Temperature Multi-Input F2D0-TI-Ex8.FF.*

FieldConnex® Fieldbus
F2D0-TI-Ex8.FF.*
  • For 8 temperature or analog sensors
  • Installation in Zone 1/Div. 1, intrinsically safe
  • Sensors in Zone 0/Div. 1
  • Connection to fieldbus acc. to FISCO or Entity
  • For FOUNDATION Fieldbus H1
  • PCS integration via device description and function blocks
  • Concentrator method for simplified configuration
  • Monitors sensor condition
  • For T/C, RTD 2-, 3-, 4-wire, voltage and resistance
  • Cold junction compensation
  • Removable terminals

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  F2D0-TI-Ex8.FF.*

Descripción del producto
Temperature multi-input, stand-alone device with aluminum housing for field installation
General specifications
Design / MountingOutside installation
Installation in hazardous areaZone 1 / Div. 1
Electronic componentTemperature Multi-Input Device RD0-TI-Ex8.FF* For technical data on installed electronic component see datasheet.
Fieldbus connection
Fieldbus typeFOUNDATION Fieldbus
Input
Number8
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Galvanic isolationEN 60079-11
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperaturesee table 1
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance10 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typeplug-in terminals , spring terminal and screw terminal
Core cross section
Busup to 2.5 mm2
Inputsup to 2.5 mm2
Cable diametersee table 2
Cable glandsensor inputs M16, fieldbus M20
Housing materialAluminum
Degree of protectionIP67
Mass1800 g
Data for application in connection with hazardous areas
EU-type examination certificatePTB 03 ATEX 2237
MarkingEx-Hexagon II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , Ex-Hexagon II (1) G [Ex ia Ga] IIC , Ex-Hexagon II (1) D [Ex ia Da] IIIC , Ex-Hexagon II 3 G Ex ic IIC T4 Gc
BusFISCO see EC-Type Examination Certificate
Inputssee EC-Type Examination Certificate
CertificatePTB 03 ATEX 2238 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Galvanic isolation
Bussee Statement of Conformity
Inputsee EC-Type Examination Certificate
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
IECEx approvalIECEx PTB 05.0001 , IECEx PTB 05.0002X
Approved forEx ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242610
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: F2D0-TI-Ex8.FF.*

Informative Literature: F2D0-TI-Ex8.FF.*

Seleccionar idioma:
LiteratureIdiomaTipo de archivoTamaño
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: F2D0-TI-Ex8.FF.*

Seleccionar idioma:
Safety and Security DocumentationIdiomaTipo de archivoTamaño
Manual de instruccionesSPAPDF229 KB
Manuals
Manual from 6.2.0 (DEV_REV 02)ENGPDF1769 KB

Design / Simulation: F2D0-TI-Ex8.FF.*

Seleccionar idioma:
CADIdiomaTipo de archivoTamaño
CAD 3-D / CAD 3-DALLSTP5195 KB

Approvals: F2D0-TI-Ex8.FF.*

Seleccionar idioma:
CertificatesNúmero de CertificadoIdiomaTipo de archivoTamaño
Brasil TUV Rheinland BrazilTÜV 13.1136ALLPDF1200 KB
Brasil TUV Rheinland BrazilTÜV 13.1134 XALLPDF1198 KB
Canada FMCoC 3025732CALLPDF316 KB
China SITIIAS CCC Ex Certificate2020322314002489 (Singapore)ALLPDF2152 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe PTB ATEX Category 2 (1)PTB 03 ATEX 2237ALLPDF884 KB
Europe PTB ATEX Category 3 GPTB 03 ATEX 2238XALLPDF617 KB
Fieldbus FoundationIT111100/02ALLPDF113 KB
India PESO (India) CCOEA/P/HQ/KA/104/5828 (P489740)ALLPDF79 KB
PTB IECEx Certificate of ConformityIECEx PTB 05.0002XALLLINK---
PTB IECEx Certificate of ConformityIECEx PTB 05.0001ALLLINK---
South Africa MASCMASC S/18-2698ALLPDF608 KB
USA FMCoC 3025732ALLPDF316 KB
Worldwide Fieldbus FoundationIT020200ALLPDF81 KB
Worldwide Fieldbus FoundationIT044400ALLPDF600 KB
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF249 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0148FALLPDF2042 KB

Software: F2D0-TI-Ex8.FF.*

Seleccionar idioma:
Device Description Files/DriversLiberar InfoTipo de archivoTamaño
DD/CFF files, Device Revision 1 / DD/CFF-Dateien, Device Revision 10107/010107ZIP62 KB
DD/CFF files, Device Revision 2, DD Revision 2 / DD/CFF-Dateien, Device Revision 2, DD Revision 20202/020101ZIP204 KB
DD/CFF files, Device Revision 2, DD Revision 3: For hosts not supporting offline dependencies / DD/CFF-Dateien, Device Revision 2, DD Revision 3: For hosts not supporting offline dependencies0203/020101ZIP204 KB

Productos asociados: F2D0-TI-Ex8.FF.*

Matching System Components
FieldConnex® Fieldbus, Temperature multi-input, electronic component for control cabinet installation, For 8 temperature or analog sensors, Installation in Zone 1/Div. 1, intrinsically safe, Sensors in Zone 0/Div. 1, Connection to fieldbus acc. to FISCO or Entity, For FOUNDATION Fieldbus H1, IECEx approval, Dust protection, International, Europe, USA, Canadapa