Servizio assistenza Sensori Industriali
Telefono: +39 039 69599 1
Fax.: +39 039 69599 30
Servizio assistenza Protezione contro le esplosioni
Telefono ++39 039 62921
Fax ++39 039 6292 390

AS-Interface power supply VAN-230/500AC-K24

VAN-230/500AC-K24
  • 8 A output load
  • 200 ... 500 VAC
  • SELV
  • LED operating display
  • AS-Interface data decoupling
  • Power factor correction

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  VAN-230/500AC-K24

Descrizione prodotto
AS-Interface power supply, data decoupling, 8 A
Indicators/operating means
LED OverloadRed LED
lights up for overload, flashes for hiccup mode
LED PWRLED green
Electrical specifications
Fusing3.15 AT (internal)
Capacity factor0.7 Capacitive at 400 VAC
Rated operating voltage195 ... 500 V AC
Rated operating current1 A at 400 VAC
Supply frequency47 ... 63 Hz
Efficiency87 %
Nominal voltage230/400 VAC
Peak inrush current< 50 A
Output
Current limitapprox. 8.5 A
Voltage31.2 V ±1 % 
Current8 A
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 50083-2:2006
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Degree of protectionIEC 60529:2001
Standard conformity
AS-InterfaceIEC 62026-2:2006
Noise immunityEN 61000-6-1:2007, EN 61000-6-2:2005
StandardsHarmonic waves: EN 61000-3-2 Class A
Interference suppression: EN 55022, EN 55011 Class B
Electrostatic discharge (ESD): IEC 61000-4-2 (8 kV contact discharge, 15 kV air discharge)
Electromagnetic fields: IEC 61000-4-3 (EN 61000-4-3; 10 V/m)
Burst: IEC 61000-4-4 (4 kV input, 2 kV output/capacitively coupled)
Surge: IEC 61000-4-5 (4 kV asymmetrical, 4 kV symmetrical)
Conducted interference: IEC 61000-4-6 (10 V, 150 kHz to 80 MHz)
Ambient conditions
Ambient temperature-10 ... 40 °C (14 ... 104 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Protection classI, Protective conductor connection necessary
ConnectionConnection terminals, max. conductor cross-section
0.5  to  2.5 mm2
Stripping length 5  to  6 mm
Massapprox. 1200 g
Dimensions
Height141 mm
Width70 mm
Length151 mm
MountingDIN mounting rail

Classifications

SystemClasscode
ECLASS 13.027040301
ECLASS 12.027040301
ECLASS 11.027040301
ECLASS 10.0.127040301
ECLASS 9.027040301
ECLASS 8.027040301
ECLASS 5.127040301
ETIM 9.0EC002540
ETIM 8.0EC002540
ETIM 7.0EC002540
ETIM 6.0EC002540
ETIM 5.0EC002540
UNSPSC 12.139121004

Details: VAN-230/500AC-K24

Design / Simulation: VAN-230/500AC-K24

Language Selection:
CADLinguaFile tipoDimensioni
CAD 3-D / CAD 3-DALLSTP100 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VAN-230/500AC-K24

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
US CA ULCoC E223176 RptRef E223176-20061107ALLPDF443 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-6843ALLPDF108 KB
Download gratuito: White paper sui protocolli di comunicazione basati su TCP (PDF)

Questo white paper gratuito in formato PDF confronta i diversi protocolli di comunicazione basati su TCP (AMQP, OPC UA, MQTT, REST API) che si sono fatti strada fino a diventare indispensabili per IIoT e Industry 4.0. Scaricalo ora gratuitamente!

Gamma dei prodotti AS-Interface

Cogli l'opportunità per conoscere la gamma completa dei prodotti AS-Interface.