Servizio assistenza Sensori Industriali
Telefono: +39 039 69599 1
Fax.: +39 039 69599 30
Servizio assistenza Protezione contro le esplosioni
Telefono ++39 039 62921
Fax ++39 039 6292 390

7500 series manifold 7500-MAN-MV-01

7500-MAN-MV-01
  • Low cost, compact design, easy to use
  • Manual valve, no electrical power requirement
  • Rugged, corrosion-resistant housing
  • Purge and pressurization valving in one device

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  7500-MAN-MV-01

Descrizione prodotto
7500 series purge and pressurization system manual manifold
General specifications
Equipment architecturemax. enclosure size 450 ft3 (12.7 m3)
Series7500
Hazardous environmentgas or dust
Pneumatic parameters
Protective gas supplycompressed air or inert gas, 5 µm filter, free from oil
Pressure requirement10 ... 120 psig (0.7 ... 8.2 bar)
Purge flow ratepressurization valve : Cv (flow coefficient) = 0.4
purging valve : Cv (flow coefficient) = 1.4
Connectionsinlet/outlet : 1/2 inch NPTF
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 80 °C (-40 ... 176 °F)
Mechanical specifications
Degree of protectionType 4X / IP66
MaterialGasket material : Bisco® HT-800 medium cellular silicone
Mass< 1.8 kg (4 lb)
Dimensionssee dimensions

Classifications

SystemClasscode
ECLASS 13.027180591
ECLASS 12.027180591
ECLASS 11.027180591
ECLASS 10.0.127291390
ECLASS 9.027291390
ECLASS 8.027291390
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121303

Details: 7500-MAN-MV-01

Informative Literature: 7500-MAN-MV-01

Language Selection:
LiteratureLinguaFile tipoDimensioni
Product Information - Pepperl+Fuchs Bebco EPS® 7500 Series Type Z/Ex pzc Purge and Pressurization SystemENGPDF682 KB

Design / Simulation: 7500-MAN-MV-01

Language Selection:
CADLinguaFile tipoDimensioni
CAD 2-D / CAD 2-DALLZIP142 KB
CAD 3-D / CAD 3-DALLSTP581 KB
CAD Portal / CAD PortalALLLINK---

Scopri il modo più intelligente per garantire la protezione delle zone pericolose e configurare il tuo sistema di purge e pressurizzazione!

Questo sistema di purge e pressurizzazione porta la protezione delle aree pericolose a un nuovo livello di innovazione e sicurezza. Ideato per aree di Classe I o II/Div. 2 e Zona 2/22, offre caratteristiche uniche in una custodia molto ridotta …