AS-Interface sensor/actuator module VAA-4E4A-G11-ZAJ/EA2L-F

VAA-4E4A-G11-ZAJ/EA2L-F
  • Inputs for 2-, 3-, and 4-wire sensors
  • Power supply of outputs from the external auxiliary voltage
  • Supply of sensors from AS-Interface
  • Function display for bus, external auxiliary voltage, in- and outputs
  • Red LED per channel, lights up in the event of output overload
  • Communication monitoring
  • Switchable lead breakage detection (outputs)
  • Cable piercing method with gold plated contact pins
  • Degree of protection IP68 / IP69K
  • AS-Interface POWER24

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  VAA-4E4A-G11-ZAJ/EA2L-F

Descrizione prodotto
G11 module
4 inputs and 4 outputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
ProfileS-7.F
IO code7
ID codeF
ID1 codeF
ID2 codeE
UL File NumberE223772
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: sensor supply i.e. overload or lead interruption outputs
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 4 LED yellow
LED OUTswitching state (output); 4 LED yellow/red
yellow: output active
red: output overload or lead interruption
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage18,0 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA (without sensors) / max. 240 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
option 2 inputs for 4-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage12 ... 31 V
Current loading capacity≤ 200 mA, overload and short-circuit protected
Input current≤ 9 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 3 mA
1 (attenuated)≥ 5 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Voltage≥ (UAUX - 0.5 V)
Current2 A per output
TB ≤ 40 °C: 6 A total
TB ≤ 70 °C: sum O1 + O2 max. 2 A, sum O3 + O4 max. 2 A
Galvanic isolation
Input/Outputsafe isolation, rated insulation voltage 40 V DC
Output/AS-Interfacesafe isolation, rated insulation voltage 40 V DC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions 3 shocks
10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: AS-Interface flat cable
Inputs/outputs: M12 round connector
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
Dimensions
Height35 mm
Diameter85 mm
MountingMounting plate

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VAA-4E4A-G11-ZAJ/EA2L-F

Informative Literature: VAA-4E4A-G11-ZAJ/EA2L-F

Language Selection:
LiteratureLinguaFile tipoDimensioni
Application Report - Automating Material Handling Systems for Airports with AS-InterfaceENGPDF272 KB

Design / Simulation: VAA-4E4A-G11-ZAJ/EA2L-F

Language Selection:
CADLinguaFile tipoDimensioni
CAD 2-D DWG / CAD 2-D DWGALLDWG392 KB
CAD 3-D / CAD 3-DALLSTP4756 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VAA-4E4A-G11-ZAJ/EA2L-F

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
Canada, USA ULCoC 20141115-E223772ALLPDF342 KB
EU Ecolab Material ResistanceECOLABALLPDF1797 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2931BALLPDF119 KB

Prodotti associati : VAA-4E4A-G11-ZAJ/EA2L-F

Accessories

Blind plug for M12 socketsfa

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
Download gratuito: White paper sui protocolli di comunicazione basati su TCP (PDF)

Questo white paper gratuito in formato PDF confronta i diversi protocolli di comunicazione basati su TCP (AMQP, OPC UA, MQTT, REST API) che si sono fatti strada fino a diventare indispensabili per IIoT e Industry 4.0. Scaricalo ora gratuitamente!

Modulo per quadri elettrici KE5 con AS-Interface – Semplicità di gestione e migliore maneggevolezza

L'esclusivo design della custodia del nuovo modulo per quadri elettrici KE5 consente una buona visibilità e semplifica le operazioni di montaggio, cablaggio e manutenzione all'interno di quadri elettrici e scatole di derivazione.

Gamma dei prodotti AS-Interface

Cogli l'opportunità per conoscere la gamma completa dei prodotti AS-Interface.