AS-Interface sensor/actuator module VAA-4E4A-KE5-ZEJQ/R

VAA-4E4A-KE5-ZEJQ/R
  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Selectable supply to the sensors: External or from the module
  • Function display for bus, internal sensor supply, inputs, and outputs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  VAA-4E4A-KE5-ZEJQ/R

Descrizione prodotto
Cabinet module
4 inputs and 4 relay outputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.0
UL File NumberE223772
MTBF224 a
Indicators/operating means
LED FAULTFault display; Red LED
red: Communication fault or address is 0
red, flashing: Overload, internal input supply
LED INTInternal input supply active; LED green
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 4 LED yellow
Electrical specifications
Auxiliary voltage (input)12 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 35 mA (without sensors) / max. 230 mA
Surge protectionO1 ... O4: Over voltage category II
UEXT, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input
Number/Type4 inputs for 3-wire sensors (PNP), DC
Supplyfrom AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT)
Voltage21 ... 31 V DC (INT)
Current loading capacity≤ 150 mA, overload- and short-circuit protected (INT)
Input current≤ 5.6 mA (max.)
Switching pointaccording to DIN EN 61131-2 (type 1)
0 (unattenuated)≤ 0.5 mA
1 (attenuated)≥ 2 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type4 relay outputs, normally open
Supplynone
Nominal load
Per contact2 A/30 VDC; 2 A/250 VAC
For more information, see the "Galvanic Isolation" section
Per module8 A
Control circuit≤ 11 mA per relay (from AS-Interface)
Switching delay< 10 ms (AS-Interface/contact)
Usage categoryDC-13 and AC-14
Switching
Mechanical5 x 107
Electrical2 x 105 (250 VAC, 2 A, cos φ = 0.4)
Galvanic isolation
Input/Outputsafe isolation, Rated insulation voltage 252 Veff
Input/AS-InterfaceSwitch position INT: None Switch setting EXT: safe isolation, rated insulation voltage 92 Veff
Output/OutputBasic insulation, rated insulation voltage 250 Veff, in phase
Output/AS-Interfacesafe isolation, Rated insulation voltage 252 Veff
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Low voltage
Directive 2006/95/ECEN 60664-1:2007
Standard conformity
Galvanic isolationEN 60664-1:2007
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Electrical safetyIEC 61140:2009
InputEN 61131-2:2004
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026:2013
Programming instructions
ProfileS-7.0
IO code7
ID code0
ID1 codeF
ID2 codeE
Data bits (function via AS-Interface)InputOutput
D0 IN1 O1
D1 IN2 O2
D2 IN3 O3
D3 IN4 O4
Parameter bits (programmable via AS-i)function
P0Communication monitoring
P0 = 0 monitoring = off, the outputs maintain the status if communication fails
P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings)
P1Input filter
P1 = 0 input filter on, pulse suppression ≤ 2 ms
P1 = 1 input filter off (default settings)
P2Synchronous mode
P2 = 0 synchronous mode on
P2 = 1 synchronous mode off (default settings)
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree2
Mechanical specifications
Degree of protectionIP20
Installation in an enclosure with a minimum protection class of IP54 required
ConnectionRemovable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass125 g
Dimensions
Height100 mm
Width18.9 mm
Length124 mm
MountingDIN mounting rail

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VAA-4E4A-KE5-ZEJQ/R

Product Documentation: VAA-4E4A-KE5-ZEJQ/R

Language Selection:
Brief InstructionsLinguaFile tipoDimensioni
Instruction leaflet / BeipackzettelALLPDF1483 KB

Design / Simulation: VAA-4E4A-KE5-ZEJQ/R

Language Selection:
CADLinguaFile tipoDimensioni
CAD 3-D / CAD 3-DALLSTP19087 KB

Approvals: VAA-4E4A-KE5-ZEJQ/R

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
AS-Interface123601ALLPDF117 KB
US CA ULE223772ALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-1953BALLPDF115 KB
UK Declaration of Conformity (P+F)TDOC-7013_ENGENGPDF172 KB

Prodotti associati : VAA-4E4A-KE5-ZEJQ/R

Accessories

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
Download gratuito: White paper sui protocolli di comunicazione basati su TCP (PDF)

Questo white paper gratuito in formato PDF confronta i diversi protocolli di comunicazione basati su TCP (AMQP, OPC UA, MQTT, REST API) che si sono fatti strada fino a diventare indispensabili per IIoT e Industry 4.0. Scaricalo ora gratuitamente!

Modulo per quadri elettrici KE5 con AS-Interface – Semplicità di gestione e migliore maneggevolezza

L'esclusivo design della custodia del nuovo modulo per quadri elettrici KE5 consente una buona visibilità e semplifica le operazioni di montaggio, cablaggio e manutenzione all'interno di quadri elettrici e scatole di derivazione.

Gamma dei prodotti AS-Interface

Cogli l'opportunità per conoscere la gamma completa dei prodotti AS-Interface.