Servizio assistenza Sensori Industriali
Telefono: +39 039 69599 1
Fax.: +39 039 69599 30
Servizio assistenza Protezione contro le esplosioni
Telefono ++39 039 62921
Fax ++39 039 6292 390

AS-Interface Safety Monitor VAS-4A16L-K31

VAS-4A16L-K31
  • Certified up to SIL 3 according to IEC 61508 and EN 62061 and up to PLe according to EN 13849
  • Stainless steel housing
  • LC display for slave addresses and error messages
  • Configuration and commissioning with configuration software
  • 2 safe output relays and 2 safe electronic outputs
  • 2 AS-Interface networks
  • Memory card for configuration data

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Scarica il Datasheet completo in formato PDF:


Estratto del Datasheet: Dati tecnici del  VAS-4A16L-K31

Descrizione prodotto
Safety Monitor, 16 decentralized output circuits
General specifications
AS-Interface specificationV3.0
PLC-Functionalitynone
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
Switch-on delay< 10 s
Response delay< 40 ms
UL File NumberE223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
MTTFd200 a
B10d2 E+7
Indicators/operating means
DisplayIlluminated graphical LC display for addressing and error messages
LED FAULTError display; red LED
red: Communication error
red flashing: release circuit error
LED POWERvoltage ON; LED green
LED U AS-i 1 / U AS-i 2AS-Interface voltage - circuit 1/circuit 2; green LED
LED readyoff: -
constantly lit: startup/restart lock active
flashing: external test required
LED AUXext. auxiliary voltage UAUX ; LED green
LED EDM/StartExternal device monitoring circuit inputs closed, 4x yellow LEDs
LED output circuitOutput circuit closed; 4 x green LEDs
Button4
Electrical specifications
Insulation voltage≥ 500 V
Rated operating voltage26.5 ... 31.6 V from AS-Interface;
24 V DC
Rated operating current≤ 200 mA from 24 VDC
≤ 45 mA from AS-Interface
Interface
Interface typeRS 232, serial
Transfer rate19.6 kbaud, no parity, 1 start bit, 1 stop bit, 8 data bits
Interface 2
Interface typeChip card slot
Input
Number/Type4 EDM/Start inputs:
EDM: Inputs for the external device monitoring circuits
Start: start inputs:
Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs)
Output
Safety outputOutput circuits 1 and 2: 2 potential-free contacts,
max. contact load:
3  ADC-13 at 30 VDC,
3 AAC-15 at 30 VAC
Output circuits 3 and 4: 2 PNP transistor outputs
max. contact load:
0.5  ADC-13 at 30  VDC
Connection
AS-Interfacespring terminals, removable
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Electromagnetic compatibilityEN 61000-6-2:2005, EN 61000-6-4:2007
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Shock resistanceEN 61131-2:2004
StandardsEN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e)
Approvals and certificates
UL approvalAn isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed.
UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Material
HousingStainless steel
Mass800 g
Dimensions
Height120 mm
Width85 mm
Length89 mm
Construction typeLow profile housing , Stainless steel

Classifications

SystemClasscode
ECLASS 13.027243101
ECLASS 12.027243101
ECLASS 11.027243101
ECLASS 10.0.127243101
ECLASS 9.027243101
ECLASS 8.027279215
ECLASS 5.127279215
ETIM 9.0EC001449
ETIM 8.0EC001449
ETIM 7.0EC001449
ETIM 6.0EC001449
ETIM 5.0EC001449
UNSPSC 12.139121535

Details: VAS-4A16L-K31

Product Documentation: VAS-4A16L-K31

Language Selection:
Product informationLinguaFile tipoDimensioni
Configuring a Safe Input on AS-Interface Safety at WorkENGPDF258 KB
Brief Instructions
Installation instructions VAS-4A16L-K31 / Montageanweisung VAS-4A16L-K31ALLPDF1543 KB
Manuals
Manual VAS-2A1L-K31 & VAS-4A16L-K31ENGPDF5570 KB
Replacing the AS-Interface consortial Safety MonitorENGPDF3164 KB

Design / Simulation: VAS-4A16L-K31

Language Selection:
CADLinguaFile tipoDimensioni
CAD 3-D / CAD 3-DALLSTP2685 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VAS-4A16L-K31

Language Selection:
CertificatesCertificato NumeroLinguaFile tipoDimensioni
US CA ULE223772ALLLINK---

Software: VAS-4A16L-K31

Language Selection:
Software Toolsinformazioni sulla liberatoriaFile tipoDimensioni
SISTEMA SLB Library AS-Interface Safety / SISTEMA SLB Library AS-Interface SafetyZIP622 KB

Prodotti associati : VAS-4A16L-K31

Accessories
Interface converter USB/RS 232fa
Software for configuration of K30 Master Monitors/K31 and KE4 Safety Monitorsfa
Interface cable for connecting the K30/K31 Safety Monitor to a PCfa